Modbus Data Registers - Advanced Energy AE 75TX Installation And Operation Manual

Table of Contents

Advertisement

Advanced Energy®
AE
?STX and
AE
1
OOTX
Inverters
Table 6-17.
Bit mapping for inverter configuration register (Continued)
Inverter Configuration
Bit
Mapping
Instructions
Transfo1
mer
wiring configuration
OxOOlO
This
bit
is:
Set if the
inve1ter
is
wired as delta
Clear
if the
inve1
ter
is
wired
as
wye
The
default
is
wye.
Utility
meter
installation
flag
OxO lOO
This
bit
is:
Set
if
the
meter
is
installed
Clear
if the
meter
is
not
installed
The
default
is
not
installed.
Modbus Data Registers
Table
6-18.
Modbus data registers
Description
Start
End
No.
of
Mod bus
Data
Notes
Register
Register
Registers Address
Type
Modbus base address
=
1000
VoltsA
L-N
1000
1001
2
41001
FLOAT ±
32 bit
IEEE
754
VoltsB L-N
1002
1003
2
41003
FLOAT
± 32 bit
IEEE
754
VoltsCL-N
1004
1005
2
41005
FLOAT
± 32 bit
IEEE
754
ClmentA
1006
1007
2
41007
FLOAT ±
32 bit
IEEE
754
Clment B
1008
1009
2
41009
FLOAT ±
32 bit
IEEE
754
Cunent
C
1010
1011
2
41011
FLOAT
± 32 bit
IEEE
754
DC input
1012
1013
2
41013
FLOAT
± 32 bit
IEEE
754
voltage
DC input
1014
1015
2
41015
FLOAT
± 32 bit
IEEE
754
cunent (see
note)
Line
1016
1017
2
41017
FLOAT
± 32 bit
IEEE
754
frequency
Line
kW
1018
1019
2
41019
FLOAT
± 32 bit
IEEE
754
Total
kWh
1020
102
1
2
4102
1
VINT
0
to
4.29e9
delivered
PVinput
1022
1023
2
41023
FLOAT ±
32 bit
IEEE
754
voltage
570-1001793-0SB
Data Monitoring
and
Controls
6-25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ae 100tx

Table of Contents