Advanced Energy
ELECTRICAL SPECIFICATIONS
Table 10‑2. AC Electrical specifications
Description
Continuous AC power
Rated apparent power
Maximum continuous
current
Maximum overcurrent
protection
Short circuit fault current
Ground type
CEC efficiency
Peak efficiency
Operational frequency
range
AC operating range
Standby losses
A‑2
Specifications for 600 Series
AE 3TL-12kW: 12 kW
AE 3TL-16kW: 16 kW
AE 3TL-20kW: 20 kW
AE 3TL-23kW: 23.2 kW
AE 3TL-12kW: 12 kVA
AE 3TL-16kW: 16 kVA
AE 3TL-20kW: 20 kVA
AE 3TL-23kW: 23.2 kVA
AE 3TL-12kW: 14.5 A
AE 3TL-16kW: 19.3 A
AE 3TL-20kW: 24.1 A
AE 3TL-23kW: 27.9 A
AE 3TL-12kW: 20 A
AE 3TL-16kW: 30 A
AE 3TL-20kW: 35 A
AE 3TL-23kW: 40 A
AE 3TL-12kW: 16.5 A
AE 3TL-16kW: 21.0 A
AE 3TL-20kW: 26.0 A
AE 3TL-23kW: 29.0 A
3 AC 480 V Wye +N
AE 3TL-12kW: 97.5%
AE 3TL-16kW: 97.5%
AE 3TL-20kW: 97.5%
AE 3TL-23kW: 98.0%
60 Hz (57 Hz to 63 Hz adjustable)
Specifications
Specifications for 1000 Series
98.2%
423 to 528 V
< 0.5 W
570-1003552-05A