Sealing The Connection Area - Kaco blueplanet 87.0 TL3 Manual

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

7.9.6
Inverter Off connection
Connect the Powador-protect (only in the case of 380/400V
blueplanet 87.0TL3 / 92.0TL3)
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1 Undo the cable fittings [ W_20]
2 Pass the connection cable through the cable fittings.
3 Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"DO1" terminal of the protective device.
4 Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"GND" terminal of the protective device.
5 Connect the other devices to one another as follows:
- wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten the cable fitting [ W_20 /
7 After commissioning: Configure the external Overvoltage protection
Powador-protect in the menu entry Properties / Functions Proper-
ties / functions.
Connecting the 3rd party device
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1 Undo the cable fittings [ W_20]
2 Pass the connection cable through the cable fittings.
3 Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"COM"(11) terminal of the protective device.
4 Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"NC" terminal of the protective device.
5 Connect the other devices to one another as follows:
- wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten the cable fitting [ W_20 /
7 After commissioning: Configure the external 3rd party device Overvoltage
protection in the menu entry Properties / functions.
7.10

Sealing the connection area

↻ The grid connection has been prepared.
1 Lift the housing cover onto the housing and loosely tighten the fastening screws.
2 Secure the housing cover by tightening all 6 screws in a diagonally opposite se-
quence [ T_25/
4.8 Nm].
» The device has been mounted and installed.
» Put the device into operation.
Page 32
1.5 Nm]
1.5 Nm]
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Powador-
x
INV
RS485
protect
OFF
A
A
B
A
B
+
-
B
GND
GND
2
1
A
B
y
x
y
RS485
INV
OFF
INV Signal
A
B
A
B
+
-
GND
GND
Fig. 38: Connecting the device to
Powador-protect
External
x
INV
RS485
device
OFF
A
A
B
A
B
B
+
-
GND
GND
2
1
y
x
B
A
y
INV
RS485
min./ max.
OFF
10-24V(+/-20%)
/15mA-1A
+
-
A
B
A
B
GND
GND
Fig. 39: Connecting the device to
the external grid protection
2
Fig. 40: Closing the housing cover
1
Housing cover
3
Screws
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
D01
GND
4
3
2
1
14 NO
11 COM
12 NC
24
21
22
INV OFF
INV ON
1