Making The Electrical Connection - Kaco blueplanet 87.0 TL3 Manual

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Legend
1
AC connection point
2
AC overvoltage protection base
3
AC earthing bolt
7.4

Making the electrical connection

NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic condi-
tions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation;
local temperature
7.4.1
Requirement for supply lines and fuse
DC-side
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Cable lug dimension w width max
Length of insulation to be stripped off
Recommended cable type
Cable lug Ø connection bolt
Tightening torque
Fitting for DC connection
Torque for cable fitting
AC-side
Max. conductor cross-section
Min. cable cross-section
Cable diameter for cable fitting
Length of insulation to be stripped off
Cable lug Ø connection bolt
Tightening torque
Connection type
Cable lug dimension w - maximum width
Ground conductor connection
Ground conductor connection tightening torque
Fuse protection for installation provided by customer (max out-
put overcurrent protection)
Fitting for AC connection
Torque for cable fitting
Interfaces
Cable diameter for cable fitting
Torque for cable fitting
RS485 connection type
RS485 terminal cable cross-section
Cable diameter for cable fitting
Torque for cable fitting
Ethernet connection type
Page 22
4
5
6
240mm² (AL or CU)
in accordance with local installation standards
16 - 28 mm
42 mm
Depending on the ring cable lug
Solar cable
10mm
30 Nm
M40
10 Nm
240mm² (AL or CU)
in accordance with local installation standards
16 - 28 mm
Depending on the ring cable lug
Bore for M10 screw
30 Nm
Cable lug
42 mm
M10
10 Nm
max. 250A
M40
10 Nm
(2x) 8 - 17 mm
4 (M25) 1.5 (M16) Nm
Spring-type terminal
0.25 - 1.5 mm²
(3x) 5 - 10 mm
4 (M25) Nm
RJ45
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
DC connection point
DC overvoltage protection
PID connection point
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3