KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3 Manual nEnglish translation of German original Authorised electrician Important safety instructions These instructions form part of the product and must be carefully read, observed and stored in a place which is freely accessible at all...
Page 2
Legal provisions The information presented in this document is the property of KACO new energy GmbH. Publication of this document, in whole or in part, is subject to the written consent of KACO new energy GmbH. KACO warranty The latest version of our warranty conditions is available for download at http://www.kaco-newenergy.com.
Operating Instructions Photovoltaik feed-in inverter Table of contents General information............ 4 Start-up options ............ 34 About this document.......... 4 Configuration and operation .......... 41 Layout of Instructions.......... 4 Initial start-up ............ 41 Identification ............. 6 Control elements ............ 41 Warnings on the device..........
When working on the PV generator, it is also necessary to switch off the DC voltage with the external DC isolator switch (e.g. at the string combiner or the KACO DC switchbox) in addition to disconnecting the PV generator from the grid.
The device features two switched Ethernet ports to enable the user to, for example, connect several devices in series if the user prefers a linear topology. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 9...
Digital inputs It is possible to enhance the device with additional digital inputs by way of an expansion module (available from KACO Customer Service). This can be used to connect a ripple control receiver or a protective shutdown system.
Page 11
Grid connection point The clean PV-current is made available at the grid connec- tion point. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 11 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
5 Remove the uppermost side section and base section from the device. » If the device is in the correct installation position: Proceed with the installation of the mount. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 17...
NOTE: Make sure that the mount is oriented correctly. » Proceed with the installation of the device. Page 18 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
NOTE: Alternatively: At this point, the screw mentioned above can be replaced with a special-purpose screw for protection against theft. » The device is installed. Proceed with the electrical installation. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 19 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Depending on the local installation specifications, it may be necessary to earth the device with a second ground connection. To this end, the threaded bolt on the underside of the device can be used. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 27...
F Attach the supplied sticker next to the name plate on the device housing where it is clearly visible. Fig. 35: Sticker DRM 0 for Australia Page 32 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
>100m), it may also be necessary to couple segments that are located further away via a glass fiber connection. Within a segment, it is possible to link KACO devices to one another as part of an Ethernet daisy-chain by way of an inte- grated switch, whereby the Segment Controller is connected at the first element in the chain.
» Pressing the Next button will take you to the next installation step. Fig. 38: Menu item:Configuration via web user interface [See sec- tion 9.4.2} Page 45] Page 34 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 35
The Cloud and portal configuration page is not currently supported. This will be enabled in a subsequent version of the firmware. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 35 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 37
Ethernet cable (uncrossed patch cable) Establishing a connection to the KACO device 1 The device must be opened in order to connect the Ethernet cable! For safety reasons, KACO therefore recommends establishing a connection via WiFi. 2 The device's communication circuit board has 3 Ethernet ports that can be used: 1.
Page 38
Ethernet ports (marked LAN1 and LAN2) should be used. These ports have an internal switch and, in their factory de- fault state, they expect to receive an IP address from a DHCP server. Page 38 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 39
Fig. 50: Start-up via Segment Controller Scope of application The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg- ment Controller. NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers are not connected to one another via the network during start-up.
Page 40
Scope of application The network infrastructure is available in full. All of the KACO devices in the segments can be reached via Ethernet using the Segment Controller assigned to them. All Segment Controllers are monitored by a central Plant Controller.
Page 46
(4) Dynamic grid support using a fast feeding of residual current [See section 10.4.2} Page 71] up to the maximum continuous current. Page 46 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 47
1 undervoltage protection to level 1 overvoltage protection. F Set reference voltage for the active control process. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 47 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 48
NOTE: This percentage relates to the nominal frequency. Password protection 2 Activate optional password protection. Status 3 Confirm the action field Page 48 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 51
Input screens for configuring the interfaces. Network Opportunity to configure the installed network. IP Settings NOTE: Parameterization of network access. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 51 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 52
User-defined 1-4: The device attempts to log on via a user-defined por- tal that you set up subsequently. Page 52 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 54
2 Maximum change in the reactive power %Smax/min in the event of a change to under-excited mode. Page 54 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 55
F Set the active power as % of rated power above which control is acti- Lock-In power vated. 0 – 100 [%] S KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 55 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 56
NOTE: The maximum number of configurable nodes depends on the selected grid type. 2 - 10 F Specify the number of nodes. Page 56 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 58
NOTE: Up to 4 characteristic curves can be configured independently and one of them can be activated for regulation each time. Page 58 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 59
1 Enter the fallback time in seconds. 3-10000000 [s] 2 Activate the action field. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 59 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 60
0 – xxx [hour] 1 Enter the hours in the input field. 2 Confirm the action field. Page 60 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 61
NOTE: Start-up options [See section 8.4} Page 34]. When the installation process is complete, the text: Installation wizard completed appears KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 61 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
If the Operating LED and the Feed-in LEDs are flashing slowly and in tandem (~ 1 s), this indicates that a function has been completed successfully. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 63...
Page 64
Procedure is carried out. Procedure completed. USB stick can be removed. F Remove the USB stick. Page 64 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 65
Notifications / function F Press the right-hand function button (> 5 secs) to commence the procedure. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 65 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 66
NOTE: Device is disconnected from the grid. NOTE: If a button is not pressed within 15 secs: Procedure aborted. Page 66 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
The maximum feed-in power S is thus reduced to the set value S Emax Page 68 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Some grid connection rules insist that the agreed reactive power be started up from every operating point of the plant without a reduction in the current active power. Considering the fact that the blueplanet 87.0 TL3 to 150 TL3 has a semi- circular P-Q operating range, a reduction in the active power is required during operation at maximum active power be- cause an apparent power reserve is not available.
Grid support by a fast feeding of residual current also lim- its the spatial extent of the incident. Page 70 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 71
The formula for calculating the dynamic reactive current that is fed for the positive or negative phase sequence voltage is: KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 71...
In this case, P(U) control is available for making optimum use of the capacity of the upstream grid. Page 72 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 73
Fig. 73: P(f) function mode 1 with hysteresis Fig. 74: P(f) function mode 2 without hysteresis, movement on the characteristic curve KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 73 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Page 75
Enhanced island detection method The new method by KACO new energy, enhanced island detection, employs a strategy to reliably detect island formation that is based on the difference in characteristic between an interconnected grid and an islanded grid, thus ensuring reli- able fast detection and prevention of false tripping.
Wait until a cooling time of at least 10 minutes has elapsed before starting the cleaning process. Page 76 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
2 Disconnect the DC side using the DC isolator switch. » After shutdown, wait at least 5 minutes before opening the device. Page 78 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
11.9 Troubleshooting The following table lists the possible status and fault messages that the KACO devices (PV and battery) can display by means of the LC display / web interface and the LEDs. No. Grid LED Text datenloggers HMI1 and...
2 You must be able to close the box completely and it must be able to accommodate the weight and size of the device. Page 86 KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
F Store the device in a dry place, in accordance with the ambient temperature range Environmental data [See sec- tion 4.3} Page 14]. KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3 Page 87 KACO blueplanet 137 TL3 KACO blueplanet 150 TL3...
Service and warranty If you need help solving a technical problem with one of our KACO products, please contact our service hotline. Please have the following information ready so that we can help you quickly and efficiently: Device name / serial number ...