5 If this is unsuccessful, please use the full domain name:
http://bp125-125TL01234567<ExternalNetworkDomainName> or http://bp87-0-87-0TL01234567<ExternalNetwork-
DomainName>
8.4.5
Starting up a plant segment
The following figure provides an example of the structure of a plant segment consisting of a Segment Controller and a cer-
tain number of KACO devices with string combiner (SC) combinations.
Ethernet
Ethernet
BP125
BP125
ARGUS
ARGUS
SC
SC
Fig. 57: Start-up via Segment Controller
Area of application
The network infrastructure already exists. All of the KACO devices in the segment can be reached via Ethernet using a Seg-
ment Controller.
NOTE: When multiple Segment Controllers are present, keep in mind that the Segment Controllers must not be connec-
ted to one another via the network during start-up.
Once start-up is complete (assignment of devices to the individual Segment Controllers), these can be connected to the
network by pressing a Main network switch.
Required components
ž Notebook with Ethernet interface and pre-prepared start-up configuration file
ž Segment Controller
Procedure
1 Connect the notebook to the Segment Controller via Ethernet (or to a switch that provides access to the Segment
Controller).
2 Upload a pre-prepared device configuration (e.g. a device configuration that has been set up successfully on a single
device).
3 Using the Segment Controller's WEB server, it is then possible to display and select all of the connected devices on
the Segment Controller that should have this configuration.
4 Once the configuration has been uploaded to the respective devices, they will go into operation automatically follow-
ing a restart.
8.4.6
Starting up an entire plant
NOTE: Configuration of the overall system via a central Plant Controller is not currently supported!
10
Note: Otherwise all inverters would be visible for the respective Segment Controller.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Notebook
Ethernet
Segment Controller *)
Ethernet
BP125
Up to 45
ARGUS
SC
*): MC blue'Log
10
Page 41