Kaco blueplanet 87.0 TL3 Manual page 102

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

No. Grid
LED Display on web interface
LED
80
Insulation meas. not pos-
sible
81
Protection shutdown grid
voltage L1
82
Protection shutdown grid
voltage L2
83
Protection shutdown grid
voltage L3
84
Protection shutdown DC link
undervoltage
85
Protection shutdown DC link
overvoltage
86
Protect. shutdown unbal. DC
link
87
Protection shutdown over-
current L1
88
Protection shutdown over-
current L2
89
Protection shutdown over-
current L3
91
Protective shutdown drop
2.5 V
97
Protection shutdown over-
current HW
100
Protection shutdown HW
overtemperature
Page 102
Status description
The insulation measurement cannot be per-
formed because the generator voltage is too
volatile.
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
Overvoltage has been detected on a con-
ductor. An internal protective mechanism has
disconnected the device to protect it against
damage.
A voltage deviation has been found in the DC
link. An internal protective mechanism has dis-
connected the device to protect it against
damage.
A voltage deviation has been found in the DC
link. An internal protective mechanism has dis-
connected the device to protect it against
damage.
Overvoltage has been found in the DC link. An
internal protective mechanism has disconnec-
ted the device to protect it against damage.
A current that has been found on a conductor
is too high. An internal protective mechanism
has disconnected the device to protect it
against damage.
See description in the event of a fault 87
See description in the event of a fault 87
-
Too much power has been fed into the grid.
Complete disconnection of the device.
The device has been switched off because the
temperatures in the housing were too high.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Action
If a fault message
appears continu-
ously, arrange for a
service to take
place. (Semicon-
ductor defective)
Check PV module
installation.
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
In case of repeated
occurrence: Notify
your authorized
electrician!
See action in the
event of a fault 87
See action in the
event of a fault 87
-
Notify authorized
electrician / KACO
Service!
Switch off AC+DC ->
Wait 5 minutes ->
Switch on AC+DC ->
if this is not success-
ful, contact the ser-
vice department
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Pers
.
E
E
E
E
E
E
E
E
E
E
-
E/K
B E