Kaco blueplanet 87.0 TL3 Manual page 50

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
Constant k positive se-
1
2
3
4
4
quence dip &
Constant k positive se-
quence swell
k 0 – 10
Constant K negative se-
1
2
3
4
4
quence dip
Constant k negative se-
quence swell
k 0 – 10
Dead band
4
1
2
3
4
0 - 100 [% Uref]
10.0
Dynamic reactive cur-
1
2
3
4
4
rent only
Off | On
Dead band mode
1
2
3
4
4
Mode 1 | Mode 2
Reference voltage
1
2
3
4
4
80 - 110 [% Unom]
100
Minimum operating
1
2
3
4
4
voltage
45 – 125.0 [% Unom]
&
Maximum operating
voltage
45 – xxx [% Unom]
Password protection
Status
Zero current threshold
1
2
3
4
4
undervoltage
0 – 80 [%Unom]
Zero current threshold
overvoltage
108 – xxx [% Unom]
Reactive current limita-
1
2
3
4
4
tion
0 – 100 % [ % Imax]
Minimum support time
1
2
4
4
3
1000 – 15000 ms
Page 50
Action in this menu/meaning
F Set amplification factor k for the pos. sequence for drop and increase
in the grid voltage.
2
F Set amplification factor k for the neg. sequence for drop and increase
in the grid voltage.
2
F Set dead band in %.
NOTE: With FRT mode activated, the pre-fault reactive current can be
added.
F If necessary, activate pre-fault reactive current.
F Select dead band mode for the active control process.
F Set reference voltage for the active control process.
Nominal value of phase neutral conductor voltage for grid. Reference
voltage for formulae (1)and (3). Adjustable in the range from level 1 un-
dervoltage protection to level 1 overvoltage protection.NOTE:  Dynamic
grid support using a fast feeding of residual current [See sec-
tion 10.3.2} Page 84]
F Set voltage range for the active control process.
F Set voltage threshold for zero current mode.
If one or more phase/phase or phase/neutral conductor voltages move
below or above the configured threshold, the inverter changes to zero
current mode. The total current is regulated to virtually zero.
F Set the reactive power limitation.
F Set the minimum support time.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3