Kaco blueplanet 87.0 TL3 Manual page 75

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Men
Display/
spec. Set-
u
Setting
tings
level
Lock-out voltage
23V – 287V
Number of nodes
2 – 10
1st node ... 10th node
Voltage | Reactive
power | Excitation
0 – 100 [% S
0 – 100%
Over-excited | un-
der-excited
Q(U) 10 nodes
Lock-in power
0 – 100 [% S
Lock-out power
0 – 100 [% S
Lock-in time
0 – 60 [s]
Lock-out time
0 – 60 [s]
Downtime
4
1
2
3
4
0 s – 10 s
Rise Outg. grad. & Fall.
Outg. grad.
increasing | decreas-
ing
1 – 60000 [% S
min]
Min. cos-phi Q1 - Min.
cos-phi Q4
Q1
Q4
Q2
Q3
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
The control is deactivated below this voltage.
Specify the number of nodes for the cos φ/(p/pn) characteristic curve
Power of the node as a percentage of the maximum power.
For the 1st node, the power must be 0%; for the last node, the power
must be 100%. The power values of the nodes must increase continu-
ously.
]
max
Note: Storage inverters only for feed-in operation
cos φ of the node
Reactive power mode Under-excited relates to inductive load, over-ex-
cited relates to capacitive load.
Power threshold, function is activated if limit value is exceeded.
]
max
Power threshold, function is activated if limit value is undershot.
]
max
Length of time that the active power must remain below the lock-in
power level before control is deactivated.
Length of time that the active power must remain below the lock-out
power level before control is deactivated.
F Set the intentional delay for the start of the Q(U) function.
NOTE: If the voltage switches from a characteristic curve section with
Q=0 to a characteristic curve section with Q≠0 under active control,
then the reactive power setting process is delayed by the set dead
time. Once the dead time has expired, the control circuit is no longer
subject to a delay and the set settling time determines the transient
behaviour.
In addition to configuring the dynamic behaviour using the transient
time corresponding to a first-order filter, the reactive power setting can
be determined by a maximum gradient - this means the maximum
change in the reactive power per time period.
/
Maximum change in the reactive power %S
max
change to over-excited mode
NOTE: The gradient is overlaid with the settling time.
In the event of a significant voltage deviation, the maximum reactive
power adjustment range can be limited by a minimum cos φ factor in
order to prevent an excessive reactive power supply and, as a result, a
significant reduction in the maximum active power that can be fed in.
Minimum cos φ in over-excited operating mode (in-feed).
Minimum cos φ in under-excited operating mode (in-feed).
Minimum cos φ in over-excited operating mode (charge).
Minimum cos φ in over-excited operating mode (charge).
/min in the event of a
N
Page 75

Advertisement

Table of Contents
loading

Table of Contents