Kaco blueplanet 87.0 TL3 Manual page 55

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
Subnet Mask
1
2
3
4
4
Default gateway
1
2
3
4
4
DNS server settings via
4
1
2
3
4
DHCP
Status
Primary DNS &
1
2
3
4
4
Secondary DNS (op-
tional)
Web Settings
1
2
3
4
4
HTTP Port
HTTPS Port
Modbus
1
2
3
4
4
Port
1
2
4
4
3
Activation
4
4
1
2
3
Status
Write access
4
1
2
3
4
Status
MQTT
1
2
3
4
4
Broker IP
Broker port
RS485
1
2
3
4
4
RS485 address
Power Control
1
2
3
4
Power Limitation
1
2
3
4
4
Internal
1
2
3
4
4
Power Limitation
Status
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
F Assign a subnet mask.
F Enter IPv4 address of the gateway.
F Activate or deactivate the DNS server from the DHCP.
On: Once the DHCP server becomes available, the IP address is automat-
ically applied and the aforementioned menu items are filled in.
Off: Apply settings manually.
1 Enter IPv4 address of DNS server.
2 Confirm the action field.
NOTE: Opportunity to set up the http ports.
F Set up the port at which the webserver can be reached.
1 Set up the safe port at which the webserver can be reached.
2 Confirm the action field.
NOTE: Option to set the Modbus port.
F Set up network port.
F Allow Modbus TCP read access.
F Allow Modbus TCP write access.
Enabling the write access allows system critical settings to be changed
over Modbus TCP. Really enable write access?
F Confirm the action field.
NOTE: The MQTT protocol is used to implement the advanced func-
tions between the Segment Controller and the inverter (in particular,
firmware updates, distribution of device configurations etc.).
1 Displays the IP address transmitted by the Segment Controller.
NOTE: The standard settings allow for successful communication
with the Segment Controller.
2 Confirm the action field.
NOTE: Option to parameterise the RS485 interface. The parameters of
the RS485 (CON901) are (as with all KACO inverters): 9600 Baud, 8n1
and cannot currently be re-configured via the web interface
NOTE: The address must not be the same as that of any other device
or data logger.
F Assign a unique RS485 bus address to the device.
Bus termination is carried out on the HMI board by means of a dip-
switch
F Confirm the action field.
Input screens for power regulation
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the internal power
limitation. This may be necessary in order to limit the maximum
power rating of the system at the grid connection point, upon the grid
operator's request.
NOTE: Opportunity to limit the power internally
F Specify the activation status.
Page 55