Ethernet Connection; Sealing The Connection Area - Kaco blueplanet 50.0 TL3 Quick Manual

Photovoltaic feed-in
Hide thumbs Also See for blueplanet 50.0 TL3:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
Fig. 13: Communication circuit board: Connection and assignment of the interfaces
1
Communication circuit board
2
ERR – Connection for fault signal relay
3
USB – Connection for update
4
Ethernet – Connection for communication
4.7.2 Insert and lay the cables
Shielding the Ethernet and RS485 cable
1 Open and close the door completely to check that the cables (1) are not subject
to tensile or compressive forces.
2 Mark the position for connecting the shield on the clamping ring (2) of the EMC
screw fitting.
3 Pull out the cables and strip them down to the mesh wire to the marked posi-
tion (approx. 10 mm).
4 Pull the cables back to the shielding point until full shielding is provided by the
clamping ring and the connecting cable cannot be displaced. [See figure 14]
[} Page 10]

4.7.3 Ethernet connection

NOTE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed.
For this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the
cable fitting through the sealing insert.
NOTE
Use a suitable category 5 network cable. The maximum length of a network segment is 100 m. Ensure that
the cable is correctly assigned. The Ethernet connection of the device supports auto-sensing. You can use
both crossed and 1:1 protectively-wired Ethernet connection cables.
↻ Connecting cable inside the device.
1 Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board.
2 Lay the Ethernet cable correctly in the lower AC supply area and loosely fasten it using the cable ties provided.
3 Tighten the cable fittings [[
4.8

Sealing the connection area

1 The requirements of protection class IP65 are met by closing the unused cable fittings with blind caps.
2 Close the housing door and lock it with a control cabinet key.
» The device has been mounted and installed.
Page 10
Ethernet
1
ERR
USB
3
2
5
6
7
8
W_29 /
4 Nm].
Photovoltaic feed-in inverter KACO blueplanet 50.0 + 60.0 TL3
Optional
Optional
H L
H L
A B
4
5
6
Optional connection of extension module
RS485 – Connection for data loggers
DIP switch – Activate terminator
INV OFF – Connection for remote controls
M25
Fig. 14: Connecting the shield to
the EMC screw fitting
INV
OFF
RS485
DIP
Optional
A B
GND
GND
7
8
1
2
M16