Country-
Level Display/
spec. Set-
Setting
tings
Frequency
1
2
3
4
4
Trip underfrequency
monitoring
Status
Number of underfre-
quency trip-off levels
1- 5
Underfrequency trip-
off
42.5 – 65 [Hz] / &
underfrequency trip-off
time for levels 1 to 5
0 – 120000 [ms]
Trip overfrequency
monitoring
Status
Number of overfre-
quency trip-off levels
1- 5
Overfrequency trip-off
45.0 – 67.5 [Hz] / &
overfrequency trip-off
time for levels 1 to 5
0 – 120000 [ms]
Password protection
Status
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
NOTE: Opportunity to monitor frequency trip-off
F Activate, if necessary.
F Specify the number of support levels.
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactivated.
F Specify the range and trip-off time.
F Activate, if necessary.
F Specify the number of support levels.
NOTE: If the grid frequency is within the deactivation range for the
duration of the deactivation time, then the function is deactivated.
1 Specify the range and trip-off time.
2 Activate optional password protection.
3 Confirm the action field.