Kaco blueplanet 87.0 TL3 Manual page 31

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Properties of the RS485 data line
Recommendation
↻ To prevent interference during data transmission:
- Observe the wire pairing when connecting DATA+ and DATA-.
Do not lay RS485 bus lines in the vicinity of live DC/AC cables.
1 Undo the cable fitting [ W_20]
2 Thread the connection cables through the cable fitting.
3 Fit the ferrite clip on the door beam around the RS485 bus line using a cable tie.
4 Lay the connection cable correctly in the lower AC supply area and loosely
fasten it using the cable ties provided.
5 Open and close the door completely to check that the connection cable is not
subject to tensile or compressive forces.
6 To connect the shield, strip the RS485 data cable from the position of the shield
terminal to the wire mesh (approx. 20 mm).
7 Clip the stripped RS485 data cable into the shield terminal.
8 Connect the connection cables to the corresponding connection terminals.
9 The following must be connected to all inverters and to the data monitor unit in
the same way:
- Wire A (-) to wire A (-) and wire B (+) to wire B (+)
- GND to GND
10 Secure cable ties.
11 Tighten the cable fittings [ W_20 /
NOTE
When using the RS485 bus system, assign a unique address to every bus device (inverter, sensor) and ter-
minate the terminal units (see the "Settings" menu) .
↻ Check whether one of the devices represents the terminal unit.
F Only activate the terminating resistor on the communication circuit board of the terminal unit using the DIP switch.
» RS485 connection made. Lay signal cable correctly.
7.9.5
Connecting external grid protection components
The contact is designed as an N/O contact and is labelled "ERR" or "Relay" on the circuit board.
Maximum contact load
DC
30 V / 1 A
↻ Connection area cover open.
1 Loosen the cable fitting to pass the signal cable through [ W_20]
2 Thread the connection cables through the cable fitting.
3 Attach the connection cables to the terminals.Overview [See section 7.9.1} Page 29]
4 Tighten the cable fitting [ W_20 /
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Li2YCYv (twisted pair) black for laying cable outside and in
the ground, 2 x 2 x 0.5 mm²
Li2YCY (twisted pair) grey for dry and damp indoor spaces, 2
x 2 x 0.5 mm²
1.5 Nm]
1.5 Nm]
Fig. 37: Assignment of twisted-pair
wires
Page 31