Kaco blueplanet 87.0 TL3 Manual page 59

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
1st node ... 10th node
1
2
3
4
4
Power | Reactive
power | Excitation
0-100%
0.3 - 1
Over-excited | un-
der-excited
Password protection
Status
Q(U)
1
2
3
4
4
Lock-In power
1
2
3
4
4
0 – 100 [%] S
Lock-Out power
1
2
3
4
4
0-20 [%] S
Lock-In time
1
2
3
4
4
0 – 60 [s]
Lock-Out time
0 – 60 [s]
Dead time
1
2
3
4
4
0 -10 [ms]
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Settling time
1
2
3
4
4
1 – 120 [s]
Minimum cos-phi Q1
1
2
3
4
4
Minimum cos-phi Q4
0 – 1
Q(U) active curve
1
2
3
4
4
1 - 4
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
F Specify the power factor for the 1st , 10th ... node as a percentage of
the maximum power.
NOTE: For the 1st node, the power must be 0%; for the last node, the
power must be 100%. The power values of the nodes must increase
continuously.
F Specify the cos ϕ of the node.
F If a reactive power not equal to 1 is selected: Select the type of
phase shift.
NOTE: Over-excited relates to a capacitive load, under-excited relates
to an inductive load.
1 Activate optional password protection.
2 Confirm the action field.
NOTE: Define Q(U).
F Set the active power as % of rated power above which control is ac-
tivated.
max
F Set the active power as % of rated power below which control is de-
activated.
max
F Set the length of time that the active power must remain above the
lock-in / lock-out power level before control is activated.
F Set the intentional delay for the start of the Q(U) function.
NOTE: If the voltage switches from a characteristic curve section with
Q=0 to a characteristic curve section with Q≠0 under active control,
then the reactive power setting process is delayed by the set dead
time. Once the dead time has expired, the control circuit is no longer
subject to a delay and the set settling time determines the transient
behavior.
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
F Set the response speed of the Q(U) control.
NOTE: In the event of a significant voltage deviation, the maximum re-
active power adjustment range can be limited by a minimum cos-φ
NOTE: in order to prevent an excessive reactive power supply and, as a
result, a significant reduction in the maximum active power that can
be fed in.
F Enter the minimum cos-φ factor for quadrants 1 and 4.
F Select the active curve.
NOTE: Up to 4 characteristic curves can be configured independently
and one of them can be activated for regulation each time.
Page 59

Advertisement

Table of Contents
loading

Table of Contents