Kaco blueplanet 87.0 TL3 Manual page 56

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
Maximum apparent
1
2
3
4
4
power Slim
1000 – S
Maximum active power
1
2
3
4
4
Plim
1.0 - 100.0 [% Slim]
Password protection
Status
External
1
2
3
4
4
Power Limitation
Status
AC fallback active
power
0 – 100 [%Plim]
Fallback time
60 – 43200 [s]
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Settling time
1
2
3
4
4
200 – 30000 [ms]
Password protection
Status
Page 56
Action in this menu/meaning
NOTE: The max. apparent power limits the internal power of the
device.
[VA]
More detailed information at:
max
Other grid-supporting functions that are effective in the case of active
power [See section 10.4} Page 86]
F Enter the value or set the value using the slider.
The apparent power is limited globally to the configured value in VA. All
active and reactive power control values use S
100 %, if S
More detailed information at:
Other grid-supporting functions that are effective in the case of active
power [See section 10.4} Page 86]
F Enter the value or set the value using the slider.
Active power is limited globally to the configured value in % S
1 Optional: Activate password protection.
2 Confirm the action field.
NOTE: The output power of the device can be set permanently to a
lower value than the maximum output power by the external power
limitation.
F Specify the activation status.
F Set the fallback power.
Specifies the default power in case of loss of communication. If no act-
ive power command is received for the configured timeout, the inverter
adapts the power to the configured fallback power.
F Set the fallback time.
Specifies the timeout period until the inverter reverts to fall back power
in case of loss of communication.
F Specify the increasing and decreasing output gradient.
1 Specify the settling time.
2 Activate optional password protection.
3 Confirm the action field.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
is configured.
lim
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
instead of S
as
lim
max
or S
.
lim
max

Advertisement

Table of Contents
loading