Kaco blueplanet 87.0 TL3 Manual page 101

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

No. Grid
LED Display on web interface
LED
62
Standalone mode
63
Frequency-dependent
power reduction
64
Output current limitation
67
Fehler Leistungsteil 1
70
Fault in fan 1
71
Fault in fan 2
72
Fault in fan 3
73
Standalone grid error
75
Self test in progress
78
Resid. current shutdown
(AFI)
79
Insulation measurement
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Status description
-
The feed-in power is reduced linearly over a
certain frequency value. This requirement is
country-dependent.
Power limitation as the max. permissible value
of the feed-in current per phase has been
reached. This is a protective function of the
device. The AC current is limited once the spe-
cified maximum value has been reached.
Es liegt ein Fehler im Leistungsteil vor.
Failure in the interior fan or the corresponding
tacho signal. The power is reduced to 50%
Pnom. All 3 LEDs light up on the device.
Failure in the 1st external fan or the corres-
ponding tacho signal. The power is not re-
duced. This occurs via the temperature dereg-
ulation. All 3 LEDs light up on the device.
Failure in the 2nd external fan or the corres-
ponding tacho signal. The power is not re-
duced. This occurs via the temperature dereg-
ulation. All 3 LEDs light up on the device.
Shutdown since an AC grid is no longer avail-
able. Standalone grid detection is only active
in certain country settings.
No fault message, only a status.
A static residual current causes the device to
shut down. The shutdown threshold is determ-
ined by the power class and the relevant regu-
lations.
The insulation resistance of the plant is calcu-
lated prior to activation.
Action
Pers
.
-
-
This is a require-
-
ment from the grid
operator.
This is a normal pro-
-
tective function of
the device.
Es liegt ein Fehler
E
im Leistungsteil vor.
Is the fan blocked?
E
For electrically
trained and quali-
fied personnel: Are
the plugs correctly
plugged in?
See action in the
E
event of a fault 70
See action in the
E
event of a fault 70
Is the grid still
B
present with all
three phases (fuses
tripped)?
-
-
If the fault tends to
E
occur in the event
of precipitation or
high levels of hu-
midity, this indic-
ates the presence of
an insulation fault
on the DC side of
the plant -> check
the DC cabling in
the plant!
Normal device re-
B
sponse Device is not
permitted to be per-
manently in this
status, however. If it
does -> fault in the
device.
Page 101