Kaco blueplanet 87.0 TL3 Manual page 54

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
Voltage
1
2
3
4
4
Trip undervoltage mon-
itoring
Status
Number of under-
voltage trip-off levels
1 - 5
Undervoltage trip-off
10 – 100 [% Unom]
&
Undervoltage trip-off
time for levels 1 to 5
0– 120000 [ms]
Trip overvoltage monit-
oring
Status
Number of overvoltage
trip-off levels
1 - 5
Overvoltage shutdown
100 – 125 - 150 [%
Unom] / &
Overvoltage trip-off
time for levels 1 to 5
0– 120000 [ms]
Password protection
Status
Overvoltage protection
1
2
3
4
4
Transient overvoltage
protection
114.8 - 148.0 [%
Unom]
Password protection
Status
Interfaces
1
2
3
4
Network
1
2
3
4
4
IP Settings
1
2
3
4
4
DHCP
1
2
3
4
4
Status
IP Address
1
2
3
4
4
Page 54
Action in this menu/meaning
NOTE: Option to monitor the voltage shutdown
F Activate if necessary.
F Specify the number of support levels.
F Define range and trip-off time.
F Activate if necessary.
F Specify the number of support levels.
1 Define range and trip-off time.
2
1 Activate optional password protection.
2 Confirm the action field.
F Set transient overvoltage protection.
NOTE: Shutdown occurs within a mains cycle.
1 Activate optional password protection.
2 Confirm the action field.
Input screens for configuring the interfaces.
Opportunity to configure the installed network.
NOTE: Parameterization of network access.
F Activate or deactivate the DHCP.
On: Once the DHCP server becomes available, the IP address, subnet
mask, gateway and DNS server are automatically applied and the afore-
mentioned menu items are filled in.
Off: Apply settings manually.
F Allocate a unique IPv4 address in the network.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3