7.9.6
Connecting "Inverter Off"
Connect the Powador-protect (only in the case of 380/400V
blueplanet 87.0TL3 / 92.0TL3)
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1 Loosen the cable fittings [ W_19]
2 Thread the connection cables through the cable fittings.
3 Connect wire A (+) to the terminal marked "INV OFF+" on the first device via the
"DO1" terminal of the protective device.
4 Connect wire B (-) to the terminal marked "INV OFF-" on the first device via the
"GND" terminal of the protective device.
5 Connect the other devices to one another as follows:
- Wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten cable fitting [ W_19 /
7 After commissioning: Configure the external Overvoltage protection
Powador-protect in the menu entry Properties / Functions Proper-
ties / functions.
Connect the external device
↻ The cable to the external grid protection device is available on the device.
↻ Cover of the device has been opened.
1 Loosen the cable fittings [ W_20]
2 Thread the connection cables through the cable fittings.
3 Connect wire A (+) from "COM" (11) on the terminal of the protective device to
the terminal marked "INV OFF+" on the first device.
4 Connect wire B (+) from "NC" (12) on the terminal of the protective device to
the terminal marked "INV OFF-" on the first device.
5 Connect the other devices to one another as follows:
- Wire A (+) to wire A (+) and wire B (-) to wire B (-).
6 Tighten cable fitting [ W_20 /
7 After commissioning: Configure the external Overvoltage protection exter-
nal device in the menu entry Properties / Functions Properties / functions.
7.10

Sealing the connection area

↻ The grid connection has been prepared.
1 Lift the housing cover onto the housing and loosely tighten the fastening screws.
2 Secure the housing cover by tightening all 6 screws in a diagonally opposite se-
quence [ T_25/ 42.48 In-Ibs ].
» The device has been mounted and installed.
» Put the device into operation.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
22 In-Ibs ]
13,27 In-Ibs ].
Powador-
x
INV
RS485
protect
OFF
A
D01
GND
A
B
A
B
+
-
B
4
3
GND
GND
2
2
1
1
A
B
y
x
y
RS485
INV
OFF
INV Signal
A
B
A
B
+
-
GND
GND
Fig. 38: Connect the device to
Powador-protect
External
x
INV
RS485
device
OFF
A
14 NO
11 COM
12 NC
A
B
A
B
B
+
-
24
GND
GND
21
22
2
1
y
x
B
A
y
INV
RS485
min./ max.
OFF
10-24V(+/-20%)
/15mA-1A
INV OFF
+
-
A
B
A
B
INV ON
GND
GND
Fig. 39: Connecting the device to
the external grid protection device
1
2
Fig. 40: Closing the housing cover
1
Housing cover
3
Screws