Kaco blueplanet 87.0 TL3 Manual page 104

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

No. Grid
LED Display on web interface
LED
119
DC overvoltage 2
125
Relay control fault
128
Internal memory error 1
129
Voltage-dependent power
reduction
148
External memory error 1
150
Protective shutdown drop
reference ADC
158
Power limitation
159
Waiting for fault acknow-
ledgement
160
Error: Grid relay L1
161
Error: Grid relay L2
162
Error: Grid relay L3
164
Error: Filter relay L1
165
Error: Filter relay L2
166
Error: Filter relay L3
169
Error: AFI sensor
180
Pre-synchronisation not pos-
sible
Page 104
Status description
PV voltage above permissible limit values.
The enable signal for the relay control is read
back. Shutdown occurs if the level is incorrect.
Write or read access to the internal RAM of
the DSP was erroneous. The device only feeds
into the grid again the next day or following a
reset.
Yes, if the function P(U) sets the power level
according to the specified parameters subject
to the AC voltage.
The device has permanent internal memory
for the purpose of, for example, storing the
hardware used. Operation parameters are de-
duced from this.
Internal protective function in order to adhere
to the required measurement accuracy.
Power limitation because the internal temper-
ature is too high. The temperature is meas-
ured on the control card. This is a protective
function of the device.
The DSP is waiting for the configuration data
from the HMI.
During the self-test, it is discovered that the
grid-side Lx relay becomes stuck. The self-test
does not check whether the relay switches on.
Grid-side Lx relay defective.
See description in the event of a fault 160
See description in the event of a fault 160
See description in the event of a fault 160
See description in the event of a fault 160
See description in the event of a fault 160
The AFI sensor is demagnetised prior to feed-
in. If this is not possible, this error message ap-
pears.
Adequate voltage pre-synchronisation with
the AC grid not possible.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
Action
Re-wire PV mod-
ules. Contact your
authorised electri-
cian.
Notify KACO Ser-
vice!
Disconnect device
on the DC side and
wait 1 minute, then
switch on again.
This functionality
may, for example,
be requested by the
grid operator. If
there is no request,
the function can be
deactivated.
Disconnect AC and
DC, wait 1 minute
and switch on again.
Disconnect AC and
DC, wait 1 minute
and switch on again.
-
Configuration of the
device must be con-
cluded in full.
Device error detec-
ted
See action in the
event of a fault 160
See action in the
event of a fault 160
See action in the
event of a fault 160
See action in the
event of a fault 160
See action in the
event of a fault 160
Device error detec-
ted
Disconnect AC and
DC, wait 1 minute
and switch on again.
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Pers
.
E
K
B
B
B
B
-
B
-
-
-
-
-
-
-
B