Kaco blueplanet 87.0 TL3 Manual page 61

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
P(f) deactivation gradi-
1
2
3
4
4
ent
0 – 60000 [% / min]
Dynamic gradient
4
4
1
2
3
mode
On | Off
P(f) minimum deactiva-
1
2
3
4
4
tion frequency
45 – 61.5 [Hz] / &
P(f) maximum deactiv-
ation frequency
45 – 70 [Hz]
P(f) settling time
1
2
3
4
4
200 – 2000 [ms]
Password protection
Status
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Voltage-dependent
4
1
2
3
4
P(U) operation mode
1
2
3
4
4
Off | On
Reference power
1
2
3
4
4
Actual power |
Nominal power
Evaluated voltage
1
2
3
4
4
Maximum phase
voltage | Positive
phase sequence
voltage
Hysteresis mode
1
2
3
4
4
Off | On
Deactivation gradient
1
2
3
4
4
0 – 65534 [% / min]
Deactivation time
1
2
3
4
4
0 – 60000000 [ms]
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
F Determine the deactivation gradient.
F Activate dynamic gradient.
F Specify the minimum deactivation frequency in Hz.
NOTE: Only evaluated in Mode 1.
The function is deactivated if the frequency re-enters the range
between minimum and maximum deactivation threshold and remains
there for the duration of the deactivation time.
1 Set the P(f) settling time mode.
2 Activate optional password protection.
3 Confirm the action field.
F Specify the increasing and decreasing output gradient.
NOTE: Activate voltage-dependent power reduction in the P(U) menu.
F Activate the control process.
Off: Deactivates dynamic grid support using dynamic reactive current.
Dynamic grid support remains active on account of immunity to inter-
ference.
F Select the power-dependent control method.
F Select the voltage to be rated.
Specifies which voltage is evaluated in a three-phase system.
NOTE: Hysteresis mode affects the shutdown response of P(U).
F Activate the mode.
F Set the gradients for the power limitation.
F Specify the time for voltage reduction.
F Specify the increasing and decreasing output gradient.
Page 61