Commissioning; Requirements; Preconditions Relating To Standards - Kaco blueplanet 87.0 TL3 Manual

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

8

Commissioning

8.1

Requirements

DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
The device is only permitted to be commissioned by a qualified professional.
Unauthorised persons must be kept away from the device.
WARNING
Risk of burns from hot surface.
Heat sinks become very hot when in operation.
Never touch the heat sinks after commissioning the device.
Allow the heat sinks at least 10 minutes to cool down before cleaning.
↻ The device has been mounted and electrically installed.
↻ The PV generator supplies a voltage above the configured start voltage.
1 Connect the grid voltage using the external circuit breakers.
2 Connect the PV generator using the DC isolator switch (0 > 1)
» The device begins operation.
» During initial start-up: Follow the instructions of the New Connection Wizard.
NOTE
A mobile terminal device with WIFI interface is required in order to put the device into operation.
The following functions are only available via the WEB interface:
Initial start-up
Parameterization
Resetting the device to its factory defaults
NOTE
We recommend using an up-to-date Firefox or Chrome browser or the default browser that is available on
the mobile terminal devices to configure the device via the web interface.
8.2

Preconditions relating to standards

Attachment of safety label in accordance with UTE C15-712-1
The code of practice UTE C15-712-1 requires that, upon connection to the French
low-voltage distribution network, a safety sticker showing a warning to isolate both
power sources when working on the device must be attached to each device.
F Attach the provided safety sticker to the outside of the device housing where it is
clearly visible.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
ATTENTION
Isoler les deux sources
Présence de deux
avant toute intervention
sources de tension
- Réseau de distribution
-Panneux photovoltaïques
Fig. 41: Safety label UTE C15-712-1