Kaco blueplanet 87.0 TL3 Manual page 57

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

Country-
Level Display/
spec. Set-
Setting
tings
Power rampup active
1
2
3
4
4
Power rampup gradi-
ent
1 – 600 [% / min]
Rampup on every con-
nect
Status
Rampup on first con-
nect
Status
Rampup after grid fail-
ure
Status
Password Protection
Status
Reactive Power Control
1
2
4
4
3
(RPC)
Mode
1
2
3
4
4
Cos-phi const. | Q
const. | Cos-phi(P/Pn)
| Q(U)
Password protection
Status
Cos-phi constant
1
2
3
4
4
cos-phi const.
0.3 - 1
Output gradient limita-
1
2
4
4
3
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Settling time
1
2
3
4
4
200 - 60000 [ms]
1000
Password protection
Status
Q constant
1
2
3
4
4
Q constant
1
2
3
4
4
0 – 100%
Under-excited |
over-excited
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Action in this menu/meaning
NOTE: Power ramp-up is used to ramp up the power gradually
F Set increase.
1 Activate option.
2 Activate optional password protection.
3 Confirm action field
NOTE: Activate the reactive power process in the mode menu.
Reactive power control [See section 10.1} Page 70]
1 Select a control process.
2 Activate optional password protection.
3 Confirm the action field.
Define cos φ constant.
F Determine the specified displacement factor.
.
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behaviour corresponds to a first-order filter (PT-1) with transient
time = 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
NOTE: Define Q specification.
F Set the idle power Q (in %) to a fixed value.
F Select the type of phase shift.
NOTE: Under-excited relates to inductive load, over-excited relates to
capacitive load.
Page 57