Country-
Level Display/
spec. Set-
Setting
tings
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Settling time
1
2
3
4
4
200 - 60000 [ms]
1000
Password protection
Status
Cos-phi
1
2
4
4
3
Lock-In voltage
4
1
2
3
4
10 – 124.8 [%
Unom]
Lock-Out voltage
1
2
3
4
4
10 – 124.8 [% Unom]
Settling time
1
2
3
4
4
0.2s – 30s
Output gradient limita-
1
2
3
4
4
tion increase & Output
gradient limitation de-
crease
1 - 65534 [% / min]
Number of nodes
1
2
4
4
3
2 - 10
Page 58
Action in this menu/meaning
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
1 Set the settling time in the event of an abrupt change in the reactive
power target value (e.g. caused by a voltage jump). The transient
behaviour corresponds to a first-order filter (PT-1) with transient
time = 5Tau.
2 Activate optional password protection.
3 Confirm the action field.
NOTE: More detailed information can be found in Reactive power
functions [See section 10.1.3} Page 73]
F Define the standard characteristic curve with 3 nodes.
F Set the voltage above which control is activated.
F Set the voltage below which control is deactivated.
F Set the settling time in the event of an abrupt change in the reactive
power target value.
NOTE: In the target value changes as a result of activating or deactivat-
ing the function by way of lock-in and lock-out voltage or changing the
active power, then the new target value is set within 10s with the
transient response of a first-order filter (PT-1) with a time constant of
Tau=2s.
NOTE: In addition to configuring the transient behavior using the set-
tling time corresponding to a first-order filter, the reactive power set-
ting can be determined by a maximum gradient - maximum change in
the reactive power per time period.
1 Maximum change in the reactive power %Smax/min in the event of
a change to over-excited mode.
2 Maximum change in the reactive power %Smax/min in the event of
a change to under-excited mode.
NOTE: The maximum number of configurable nodes depends on the
selected grid type.
F Specify the number of nodes.
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3