Kaco blueplanet 87.0 TL3 Manual page 103

Photovoltaic feed-in inverter
Hide thumbs Also See for blueplanet 87.0 TL3:
Table of Contents

Advertisement

No. Grid
LED Display on web interface
LED
101
Temperature plausibility er-
ror
102
Plausibility fault efficiency
105
Relay plausibility error
107
Check surge protection
device
108
Grid failure overvoltage L1
109
Grid failure overvoltage L2
110
Grid failure overvoltage L3
111
Grid failure undervoltage L1 See description in the event of a fault 108
112
Grid failure undervoltage L2 See description in the event of a fault 108
113
Grid failure undervoltage L3 See description in the event of a fault 108
118
DC overvoltage 1
KACO blueplanet 87.0 TL3 KACO blueplanet 92.0 TL3 KACO blueplanet 110 TL3 KACO blueplanet 125 TL3
KACO blueplanet 137 TL3 KACO blueplanet 150 TL3
Status description
The individual temperatures in the device are
compared with one another. This fault occurs
if a certain limit value is exceeded.
The degree of efficiency of the device must re-
main within certain limits.
Check the voltage measurement upstream of
and between the relays - the difference can be
a maximum of 24 V
Surge protection device (if present in the
device) has tripped and must be replaced. AC,
DC & interfaces are monitored for triggered
surge protection. All 3 LEDs light up on the
device.
Shutdown because the grid voltage on phase
Lx is outside the set limit value (2nd level up to
5th level of grid monitoring). The limit value is
specified by the respective country-specific
standard.
See description in the event of a fault 108
See description in the event of a fault 108
PV voltage above permissible limit values.
Action
Pers
.
Notify KACO Ser-
K
vice!
Notify KACO Ser-
K
vice!
Switch off the
K
device entirely
(switch off AC + DC
for min. 5 minutes),
if the fault occurs
again, there is a
device fault
Check surge protec-
K
tion in the device.
The surge protec-
tion module has a
corresponding func-
tion display. With a
red function display,
the surge protection
module must be
checked, and re-
placed if necessary.
The device feeds
back into the grid.
Check grid voltage
E
at the device ter-
minal Lx. Check set-
ting values in the
parameters menu.
Has everything been
set up correctly and
is the voltage within
the set limit values?
Check connection/
cabling!
See action in the
-
event of a fault 108
See action in the
-
event of a fault 108
See action in the
-
event of a fault 108
See action in the
-
event of a fault 108
See action in the
-
event of a fault 108
Re-wire PV mod-
E
ules. Contact your
authorised electri-
cian.