Start/Stop Lithium Battery - Ingeteam INGECON SUN STORAGE 1Play Technical Manual

Battery inverter
Hide thumbs Also See for INGECON SUN STORAGE 1Play:
Table of Contents

Advertisement

INGECON SUN STORAGE 1Play
Figure 17: Equalization process
Important note: As seen on the graph, the battery will be exposed to a higher voltage than usual, so it is very
important to ensure before using the "Manual equalization" that the battery is fully compatible with this option.
During the equalization charge, the battery must be kept cool and under close observation for unusual heat
rise and excessive venting. Some venting is normal and the hydrogen emitted is highly flammable. The
battery room must have good ventilation as the hydrogen gas becomes explosive.

6.3 Start/Stop Lithium Battery

6.3.1 When do I use this functionality?
Start/Stop lithium battery functionality is only used to switch on/off the Dow-Kokam manufacturer´s Lithium
Battery. This battery management system (BMS) needs to receive an external signal to wake-up the battery
system from the ISS 1Play Digital Output.
Don´t use this functionality for any other battery manufacturers.
6.4 Test Fans
6.4.1 Is it possible to do a fan test with the ISS 1Play?
Yes, it is possible. It is located in the display in the following path:
MAIN MENU > MORE OPTIONS > TEST FANS
This function has been developed to launch the internal and external fans for a short period of time (30
seconds).