Events - Ingeteam INGECON SUN PowerMax TL B Series Installation And Operation Manual

Table of Contents

Advertisement

Ingeteam
String13
Current string 13.
String14
Current string 14.
String15
Current string 15.
Total
Energy
Total energy fed through the inverter throughout its useful life.
Time
Total time that the inverter has been feeding the grid.
Connections Total number of grid connections.
Partial
Energy
Partial energy fed by the inverter.
Time
Partial time that the inverter has been connected to the grid.
Connections Partial number of grid connections.
Pac
AC power, in watts
Pwatt
Power fed to the public grid in self consumption mode, in watts.
Ratio
Self consumption ratio. Displays the consumption percentage of the loads being fed by the power
generated by the inverter.

19.6.2. Events

This menu shows the events occurring in the inverter.
Alarms
The alarms indicate current events in the inverter that lead to its shut-down.
Name
Variable
Overvoltage
Voltage difference
Panel overcurrent
AC zero sequence
current
BUS overvoltage
Instantaneous AC
overvoltage
AC rms voltage or
AC frequency
Instantaneous AC
overcurrent
AC rms overcurrent
128
Code
LED Lighting
1
0x0001
1
0x0002
1
0x0004
1
0x0008
1
0x0010
1
0x0020
0x0040
1
0x0200
1
0x0080
1
0x0100
Alarm
This alarm displays when there is an input voltage in the
panel (PV) above the unit's limit.
Orange
This voltage is read before the motorized switch,
specifically on the panel input string grouping plates.
The difference between the panel and bus voltage
Orange
measurements, both sides of the DC switch, is greater
than the expected limit.
Red
DC current above the limit allowed by the unit.
The instantaneous sum of the AC currents exceeds a
Red
maximum value.
There is overvoltage exceeding the maximum DC voltage
Red
limit.
The instantaneous AC voltage in one of the three phases
Orange
exceeds the unit's HW limit.
The network voltage in one or several phases is outside
of the limits established in the unit's settings for a period
above that defined in the settings. This alarm can be
instantaneous or permanent, depending on the duration
Orange
of the fault.
The unit's voltage and frequency relays are configured
according to the limits established in the regulations
applicable to each installation.
The instantaneous AC current in one of the three phases
Red
exceeds the unit's instantaneous limit.
The AC rms current in one of the three phases exceeds
Red
the unit's instantaneous limit.
ABQ2026IQE01_A - Installation and Operation Manual
Display control
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents