Supply cable fuses

Fuses for short circuit protection of the supply cable are listed below. The fuses also
protect the adjoining equipment of the drive in case of a short circuit. Check that the
operating time of the fuse is below 0.5 seconds. The operating time depends on the
supply network impedance and the cross-sectional area and length of the supply
cable. See also chapter
Note: Fuses with a higher current rating must not be used
1Φ AC supply
Drive type
Input
MFE190-04xx...
current
(A)
-01A6-2
-03A0-2
-06A0-2
14
-09A0-2
20
3Φ AC supply
Drive type
Input
MFE190-04xx...
current
(A)
-01A6-2
-03A0-2
-06A0-2
-09A0-2
12
Planning the electrical
IEC fuse
Rated
Voltage
current
(V)
(A)
3
500
7
500
20
500
500
IEC fuse
Rated
Voltage
current
(V)
(A)
2
500
4
500
20
8
500
500
installation.
UL fuse
Class Rated
Voltage
current
(V)
(A)
gG
600
gG
600
20
gG
600
gG
600
UL fuse
Class Rated
Voltage
current
(V)
(A)
gG
600
gG
600
20
gG
600
gG
600
Technical data 151
Cross-sectional
area of cable
UL
AWG
2
mm
Class
1.5...4
16...12
1.5...4
16...12
CC
1.5...4
16...12
1.5...6
16...10
Cross-sectional
area of cable
UL
AWG
2
mm
Class
1.5...4
16...12
1.5...4
16...12
CC
1.5...4
16...12
1.5...6
16...10