Routing the cables

Route the motor cable away from other cable routes. Motor cables of several drives
can be run in parallel installed next to each other. It is recommended that the motor
cable, input power cable and control cables be installed on separate trays. Avoid long
parallel runs of motor cables with other cables in order to decrease electromagnetic
interference caused by the rapid changes in the drive output voltage.
Where control cables must cross power cables make sure they are arranged at an
angle as near to 90 degrees as possible. Do not run extra cables through the drive.
The cable trays must have good electrical bonding to each other and to the grounding
electrodes. Aluminum tray systems can be used to improve local equalizing of
potential.
A diagram of the cable routing is below.
Supply cable
min 200 mm (8")

Control cable ducts

24 V 240 V
Not allowed unless the 24 V cable is
insulated for 240 V or insulated with
an insulation sleeving for 240 V.
90°
Control cables
Drive
min 500 mm (20")
90°
90°
min 500 mm (20")
Lead 24 V and 240 V control cables
in separate ducts inside the cabinet.
Planning the electrical installation 47
Supply cable
min 300 mm (12")
Motor cable
Braking resistor cable
Motor cable
24 V
240 V