Safety What this chapter contains The chapter contains the safety instructions which you must follow when installing, operating and servicing the drive. If ignored, physical injury or death may follow, or damage may occur to the drive, motor or driven equipment. Read the safety instructions before you work on the drive.
• The drive is not field repairable. Never attempt to repair a malfunctioning drive; contact your local ABB representative or Authorized Service Center for replacement. • Make sure that dust from drilling does not enter the drive during the installation.
Operation and start-up These warnings are intended for all who plan the operation, start up or operate the drive. WARNING! Ignoring the following instructions can cause physical injury or death, or damage to the equipment. • Before adjusting the drive and putting it into service, make sure that the motor and all driven equipment are suitable for operation throughout the speed range provided by the drive.
ACS350 User’s Manual. Scope This supplement is intended to be used with the ACS350 Drives (0.37...22 kW, 0.5...30 HP) User’s Manual (3AFE68462401). The supplement covers differences between the standard ACS350 and the ACS350 with IP66 casing (option +B063).
Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type code and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives...
ACS350 User’s Manual Check the insulation of the input cable, the motor and Electrical installation: Checking the insulation of the motor cable. the assembly in the ACS350 User’s Manual. Connect the power cables. Electrical installation: Connecting the power...
The chapter describes the construction and type code information in short. Overview The ACS350 with IP66 casing is a wall mountable drive for controlling AC motors. The construction of frame sizes R1 and R3 varies to some extent. Covers on (R1)
Page 18
Covers on (R3) Covers off (R3) 1 Cooling element 9 EMC filter grounding screw (EMC). 2 Mounting holes 10 Varistor grounding screw (VAR) 3 Control Panel 11 Fieldbus adapter (serial communication module) connection 4 Front cover 12 I/O connections 5 Panel connection 13 Input power connection (U1, V1, W1), brake resistor 6 Option connection connection (BRK+, BRK-) and motor connection (U2,...
You find the type code on the type designation label attached to the drive. The first digits from the left express the basic configuration, for example ACS350-03E- 08A8-4. The optional selections are given after that, separated by + signs, for example +K451.
The chapter describes the mechanical installation procedure of the drive. Unpacking the drive The package contains the following items: • (1) ACS350 with IP66 casing and Assistant Control Panel (frame size R3 shown in the figure) • (2) user’s manual and (3) IP66 supplement •...
XXXX: Integer starting every week from 0001 $ PLQ « +] 5 ABB MRP code of the drive 6 CE marking, NSF mark and RoHS mark (the label of Type designation label your drive shows the valid markings) Before installation See the ACS350 User’s Manual.
3. Position the drive onto the screws on the wall. 4. Tighten the screws in the wall securely. Attaching the optional fieldbus module See the ACS350 User’s Manual. Installing the pressure compensation valve (optional, +C169) 1. Remove the M12 plug from the gland plate.
Installing the cable glands (optional, +H376) 1. Remove the sticker labeled REMOVE BEFORE USE. 2. Tighten the cable glands that you want to use with their back nuts. The tightening torque depends on the cable gland size: • M12: 3 N·m •...
Make sure that the drive is disconnected from the input power during installation. If the drive is already connected to the input power, wait for 5 minutes after disconnecting the input power. Checking the insulation of the assembly See the ACS350 User’s Manual. Electrical installation...
Use a separate grounding cable if the conductivity of the cable shield is insufficient (smaller than the conductivity of the phase conductor) and there is no symmetrically constructed grounding conductor in the cable (see section Selecting the power cables in the ACS350 User’s Manual). L and N are connection markings for 1-phase supply.
1. On IT (ungrounded) systems and corner grounded TN systems, disconnect the internal EMC filter by removing the EMC screw. For 3-phase U-type drives (with type code ACS350-03U-), the EMC screw is already removed at the factory and replaced by a plastic one.
Mechanical installation: Free space around the drive page 22.) The motor and the driven equipment are ready for start. (See Planning electrical installation: Motor selection in the ACS350 User’s Manual and Technical data: Motor connection page 40.) ELECTRICAL INSTALLATION (See Planning electrical installation and Electrical installation.)
Ignoring the safety instructions can cause injury or death. Maintenance intervals If installed in an appropriate environment, the drive requires very little maintenance. The table lists the routine maintenance intervals recommended by ABB. Maintenance Interval Instruction...
Replacement fans are available from ABB. Do not use other than ABB specified spare parts. The factory setting for the operating hour counter (parameter 2901, see the ACS350 User’s Manual) is 23 000 hours. The Notice Handler Assistant informs you when the drive has been in use for the defined number of hours.
Internal fan replacement 1. Stop the drive and disconnect it from the AC power source. 2. Remove the front cover. 3. Open the screw(s) holding the fan in place (1 screw in R1, 2 screws in R3) 4. Free the fan cable from the clip. 5.
Technical data What this chapter contains The chapter contains the technical specifications of the drive, e.g. the ratings, sizes and technical requirements as well as provisions for fulfilling the requirements for CE and other marks. Technical data...
Current and power The current and power ratings are given below. The symbols are described below the table. Type Input Output Frame size ACS350… (+B063) 2,1min/10min 2max x = E/U 3-phase U = 200…240 V (200, 208, 220, 230, 240 V) 03x-02A4-2 0.37...
(all digital inputs in the on state and the panel, fieldbus and fan in use). The total heat dissipation is the sum of the heat dissipation in the main and control circuits. Type Heat dissipation Air flow ACS350- Main circuit Control circuit x = E/U Rated I...
Power cable sizes and fuses See the ACS350 User’s Manual. Power cables: terminal sizes, maximum cable diameters and tightening torques See the ACS350 User’s Manual. Dimensions, weights and noise Frame Dimensions and weights Noise size IP66 Weight Noise level 12.0 13.6...
The DC capacitors contain electrolyte, which is classified as hazardous waste within the EU. They must be removed and handled according to local regulations. For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor. Technical data...
Applicable standards The drive complies with the following standards: • IEC/EN 61800-5-1 (2003) Electrical, thermal and functional safety requirements for adjustable frequency a.c. power drives • IEC/EN 60204-1 (1997) + Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Amendment A1 (1999) Provisions for compliance: The final assembler of the machine is responsible for installing - an emergency-stop device...
First environment (drives of category C2) 1. The optional EMC filter is selected according to the ABB documentation and installed as specified in the EMC filter manual. 2. The motor and control cables are selected as specified in this manual.