120 Fault tracing

Controller warnings

Code
Warning
40006
Attempt to configure too
many axes
(_ecTOO_MANY_AXES)
40007
CamBox segments have
been skipped
(_ecCAM_BOX_OVERRUN)
40012
A host event has failed with
retries
(_ecEVENT_RETRY_WAR
NING)
40013
Attempted to assign too
many servo axes
(_ecTOO_MANY_SERVO_
AXES)
40014
Attempted to assign too
many stepper axes
(_ecTOO_MANY_STEPPER
_AXES)
40015
Attempted to assign too
many virtual axes
(_ecTOO_MANY_VIRTUAL
_AXES)
40016
Attempted to assign too
many remote axes
(_ecTOO_MANY_REMOTE
_AXES)
40021
All controller warnings
cleared
(_ecCONTROLLER_WARNI
NGS_CLEARED)
40022
Last reset was not controlled
(_ecRESET_NOT_CONTR
OLLED)
Cause
The device configuration file
has attempted to assign
more axes than are
available on the controller.
The cam box has skipped a
segment. This can happen
if the source is moving fast
enough to cause a
segment to be skipped.
A host (i.e. ActiveX) event
handler has failed to
acknowledge an event that
has been raised by the
controller. There is a 'time-
out' period of 1 second in
which the host must
acknowledge an event.
During the processing of the
..CMCF / .DCF (device
configuration file), too many
servo axes were configured.
During the processing of the
..CMCF / .DCF (device
configuration file), too many
stepper axes were
configured.
During the processing of the
..CMCF / .DCF (device
configuration file), too many
virtual axes were
configured.
During the processing of the
..CMCF / .DCF (device
configuration file), too many
remote axes were
configured.
This information message
can appear in the error log
to indicate that all controller
warnings have been
cleared.
Last reset was not
controlled
What to do
Re-run the System Configuration Wizard .
See CAMBOX in Mint WorkBench Help,
look at "position_array". Either slow down
the source or increase the size of the
segments
If the host does not acknowledge the event
after 3 time-out periods, the controller
generates warning 40012. See ERRDATA
for details of the error.
To fix this issue, use the System Config
Wizard to reduce the number of configured
servo axes.
To fix this issue, use the System Config
Wizard to reduce the number of configured
stepper axes.
To fix this issue, use the System Config
Wizard to reduce the number of configured
virtual axes.
To fix this issue, use the System Config
Wizard to reduce the number of configured
remote axes.
No Action Required
To fix this issue, use the System Config
Wizard to reduce the number of configured
servo axes.