Do not block the air vents on the top and bottom of the case.

Wiring

For thermocouple input, use the designated compensation lead; for RTD input, use wires with small lead wire
resistance and without any resistance difference among the three wires.
To avoid noise conductor effects, input signal wires should be separated from electric power lines or load lines.
Input signal wire and output signal wire should be separated each other. And both should be shield wire.
If there is a lot of noise from the power source, adding an insulation transducer and using a noise filter is
recommended. Always attach a noise filter to a panel that is grounded securely, and keep the wiring between
the noise filter output side and the measuring equipment power terminal wiring to a minimum length. Please do
not attach fuses and switches, etc. to the noise filter output wiring; otherwise the filter's effectiveness will be
decreased.
Twisting the power wires is effective when connecting the wires. (The shorter the pitch of the twist, the more
effective the connection is against noise.)
Operation preparation time is required for the contact output when power is turned on. If using it as a signal to an
external interlock circuit, please couple it with a delayed relay.
Concerning the output relay, connecting the maximum rated load will shorten the product's life; so please attach
an auxiliary relay. If the output operation frequency is high, selecting a SSR drive output type is recommended.
[Proportionate cycles] Relay output: 30 seconds or more, SSR drive output:
1 second or more
When inductive loads such as magnetic opening/closing equipment, etc. as relay output equipment are connected,
use of a surge absorber is recommended in order to protect the contacts against opening/closing surges and to
ensure long-term use.
Recommended specification for the surge absorber
Voltage
Nominal varistor voltage
100V
200V
Attachment position: between the relay control output contacts.

Operation

The alarm function does not work properly when an error takes place unless the settings are made correctly.
Always verify its setting before operation.
If the input wiring breaks, the display will read "UUUU" or "LLLL". When replacing the sensor, always turn the
power OFF.

Others

Please do not wipe the equipment with organic solvents such as alcohol or benzene, etc. If wiping is necessary,
use a neutral cleaning agent.
Do not use mobile phones near this equipment (within 50 cm). Otherwise a malfunction may result.
Trouble may occur if the equipment is used near a radio, TV, or wireless device.
This equipment should be treated as an industrial waste when it is disposed of.