Parameter functions and setting procedure
SV-L SV (Set value) lower limiter (091)
SV-H SV (Set value) upper limiter (092)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
These parameters specify the setting range of the SV. You can set
any value within the measurement range.
Setting range
0 to 100%FS
The relationship between SV limits and the measurement range
●
is as shown in the right figure:
Set [P-SL], [P-SU], and [P-dP] before setting SV-L and SV-H. (see page 43 to 45)
●
SVs set before setting the SV limits (Local SV, etc.) are affected by new SV limits.
●
Make sure to set the value of [SV-H] greater than [SV-L].
●
[Setting example] Setting the lower SV limit to 50°C –––––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Press and hold the
key for about five seconds during the SV/PV display.
appears.
➔
➔
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
➔
Press the
or
keys to change " 0 " to " 50 ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
➔
Process Variable
PV input
upper limit
PV input
range
PV input
lower limit
Operating procedure
.
58
SV upper limit
SV lower limit
(upper limit > lower limit)