[Loc] Key Lock (019) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

LoC Key lock (019)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Prevents SV parameters from being changed.
Setpoint
0
Unlocked (reset)
1
All settings are unchangeable from the controller, but changeable via communication.
Only the SV is changeable from the controller, and all settings are changeable via communication.
2
3
All settings are changeable from the controller, but unchangeable via communication.
4
All settings are unchangeable from the controller or via communication.
Only the SV is changeable from the controller, but all settings are unchangeable via communication.
5
When the keylock is set to 1, 2, 4, or 5, the KEYLOCK indicator lights. (see page 11)
You can view the parameters regardless of the keylock setting.
[Setting example] Changing the keylock setting to 2 –––––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Press and hold the
key for about one second during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
key to change " 0 " to " 2 ."
Press the
key or wait for three seconds to save the change.
➔ Keylock is activated.
Press the
key.
➔ The screen returns to the SV/PV display.
Description
Operating procedure
.
29
1st block parameter