2-3 Parameters List
The following explains each channel parameter.
The range of the parameters in the shaded area indicates the industrial values.
●
When you change the PV input lower limit (P-SL), PV input upper limit (P-SU), or decimal place position (P-dP),
reconfigure all the industrial values.
Power-cycle the controller after you change the setpoint of the parameters of which No. column is shaded in gray.
●
Operation Mode
Parameter
Parameter name
symbol
PV
Process Value
SV
Set value
MV
Manipulated Variable (%)
1st block parameter
Parameter
No Display
symbol
1
MANU
Manual mode selection
2
Stby
Standby setting
4
PRoG
Ramp soak control
5
LACH
Alarm latch cancel
6
At
Auto-tuning
7
tM-1
Timer 1 display
8
tM-2
Timer 2 display
10
AL1
Set value of alarm 1
11
A1-L
Lower limit value of alarm 1
12
A1-H
Upper limit value of alarm 1
13
AL2
Set value of alarm 2
14
A2-L
Lower limit value of alarm 2
15
A2-H
Upper limit value of alarm 2
19
LoC
Key lock
―
Within the limit of 0 to 100% of FS
-5.0 to 105.0 (%)
Parameter name
oFF, oN
oFF, oN
oFF, RUN, HLd
oFF, RSt
oFF, oN, L-oN
―
―
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
Absolute value alarm: 0 to 100%FS,
Deviation alarm: -100 to 100%FS
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
Absolute value alarm: 0 to 100%FS
Deviation alarm: -100 to 100%FS
0 to 5
Setting range
Setting range
default setting
15
Parameters List
Factory default
Parameter
setting
mask DSP
―
―
0
―
(°C)
DSP14-
-5.0
32768
Factory
Parameter
Reference
mask DSP
oFF
DSP13-32
oFF
DSP1-1
oFF
DSP1-2
oFF
DSP1-4
oFF
DSP1-8
―
DSP1-16
―
DSP1-32
10 (°C)
DSP1-128
10 (°C)
DSP2-1
10 (°C)
DSP2-2
10 (°C)
DSP2-4
10 (°C)
DSP2-8
10 (°C)
DSP2-16
0
DSP3-1
page
20
21
22
24
25
27
28
29