[Plc1] [Phc1] Out1 Upper/Lower Limits (104, 105) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

Parameter functions and setting procedure
PHC1 OUT1 Upper/Lower Limits (104, 105)
PLC1
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This parameter specifies the upper and lower limits for output control.
Parameter
Lower limit Upper limit
PLC1
PHC1
Related parameters: Output limit types [PCUt] (see page 63)
Be sure to set the values so that PHC is greater than PLC.
[Setting example] Setting the OUT1 lower limit to 5.0% –––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Setting range
-5.0 to 105.0 (%)
Press and hold the
key for about five seconds during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
key to change " -5.0 " to " 5.0 ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
.
62
100 (%)
PHC
PLC
0
100 (%)
Input