[Sv-1] To [Sv-8] 1St Target Sv To 8Th Target Sv (056 To 077); [Tm1R] To [Tm8R] 1St Ramp Time To 8Th Ramp Time (057 To 078); [Tm1S] To [Tm8S] 1St Soak Time To 8Th Soak Time (058 To 079) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

SV-1 to SV-8 1st target SV to 8th target SV (056 to 077)
tM1R to tM8R 1st ramp time to 8th ramp time (057 to 078)
tM1S to tM8S 1st soak time to 8th soak time (058 to 079)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Sets the ramp soak SV, ramp time and soak time.
Parameter
SV-1 to SV-8
tM1R to tM8R
tM1S to tM8S
The segment that both ramp time and soak time are set to 0.00 will be skipped.
[Example] In the example below, the step 2 is skipped.
SV-1: 50
SV-2: 200
tM1R: 0.10
tM2R: 0.00
tM1S: 0.05
tM2S: 0.00
The SV limit function ([SV-H], [SV-L]) is in effect while ramp soak is running.
The set value (SV-n) does not change, but the value is limited during ramp soak. For the above reason, the value
may not change at the set times and the ramp soak runs with the following pattern.
SV
SV-1
Step1 ramp time (tM1R)
Setting range
SV lower limit (SV-L) to SV upper limit (SV-H) %FS
00.00 to 99.59
00.00 to 99.59
SV-3: 100
tM3R: 1.00
tM3S: 0.75
SV
SV-1
SV-H
SV-2
SV-L
PV
SV-3
tM1R
SV-2
Step1 soak time (tM1S)
Step2 ramp time (tM2R)
Step2 soak time (tM2S)
SV
200
100
50
tM1R
Program pattern
Pattern with
SV limit applied
tM1S tM2R
tM2S
tM3R
53
2nd block parameter
tM1S
tM3R
t
tM3S
t