Stby Standby setting (002)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to switch between run and standby.
Setpoint
oFF
oN
STBY indicator lights during stanby. (see page 11)
When hold alarms is on, the hold function activates when you switch the standby setting from " oN " to " oFF ."
If the instrument is put into standby during auto tuning, the auto tuning is canceled. To complete auto-tuning, turn
standby setting " oFF " and restart auto tuning.
When the controller switches to standby mode, the ON delay timer will be reset. It will begin again when standby
setting is turned off.
[Setting example] Switching to Standby mode ––––––––––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Description
Operation mode
Standby mode
Press and hold the
key for about one second during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔The setpoint starts blinking.
keys to change " oFF " to " oN ."
Press the
or
Press the
key or wait for three seconds to save the change.
➔Now the controller is in the standby mode.
Press the
key.
➔The screen returns to the SV/PV display.
Operating procedure
.
21