Fuji Electric PUM Series Instruction
Fuji Electric PUM Series Instruction

Fuji Electric PUM Series Instruction

Enhanced communication module
Hide thumbs Also See for PUM Series:

Advertisement

Quick Links

PUM Series
Multi-loop module type
Temperature controller
DATA SHEET
PUMCM is the communication module to connect the module
type temperature controller, PUM series, to Mitsubishi's PLC
(MELSEC-Q/A/AnS/FX series) without program.
High-speed communication of maximum 230.4kbps can be
performed via RS-232C, RS-422 or RS-485 interface. Also,
maximum of 16 units (64 channels) of PUMA (control module)
can be connected to one of this module,and maximum 8
units of this module can be connected to 1 communication
port, and it realizes a labor saving wiring, simple engineering
and small space.
FEATURES
I. Programless connection with Mitsubishi's PLC
1. RS-232C, RS-422 or RS-485 high-speed communication
(max. 230.4 kbps)
2. Accessible to the almost all parameters of control
module (PUMA/PUMB)
3. High-speed data loading and setting reflection by high-
speed internal communication with connected control
module (PUMA/B)
4. 1:N configuration is available, which maximum 8 units
of this module can be connected to 1 communication
port.
II. User-friendly structure and functions
1. Lateral connection to 1 unit of this module: Max. 16
units (64 channels) + event input/output module 16
units = total 32 units
Simple wiring for power supply and a labor saving wiring
for communication by programless communication.
2. Detachable structure: Terminal block, main unit, and
the base part.
o Easy wiring with detachable terminal block
o Main units exchangeable without re-wiring
SYSTEM SPECIFICATION
1. Product type: Multi-loop module type temperature
controller
2. Module type
1) Analog module: Total max. 16 units
a) Control module (4 loops)
b) Enhanced input/output (analog) module
- Analog input/output module
- Analog input module (input 4 points/unit)
- Analog output module (output 4 points/unit)
2) Enhanced input/output (digital) module:
- Event input/output module
3) Enhanced communication module: 1 unit
ENHANCED COMMUNICATION MODULE [PUMCM]
(Mitsubishi's PLC Programless Communication)
(input/output 4 points/unit)
Maximum 16 units
(input/output 8 points/unit)
3. Connecting method:
Lateral connecting with connectors
(For power supply and RS-485 commu-
nication, any one of connected modules
is required to be connected)
4. No. of loop, input/output
1) Control loop:
Max. 64
2) No.of input / output: DI 128 points / DO 128 points
ENHANCED COMMUNICATION MODULE

SPECIFICATIONS

(Mitsubishi's PLC programless communica-
tion)
1. General specification
(1) Power supply: 24V DC ±10%
(2) Power consumption: Max. 3.2 W (135 mA)
(3) Insulation resistance: 20M: or more (500V DC)
(4) Withstand voltage:
Power supply l loader communication
Power supply l RS-232C,RS-422,RS-485
(5) Applied standards:
UL, C-UL, CE marking, RoHS directive
[Pending for UL, C-UL marking]
PUMCM
[when 24V DC is applied]
1000V AC 1 min.
1000V AC 1 min.
EDS11-168b
Date
Apr. 1, 2011

Advertisement

Table of Contents
loading

Summary of Contents for Fuji Electric PUM Series

  • Page 1: Specifications

    Temperature controller DATA SHEET PUMCM PUMCM is the communication module to connect the module type temperature controller, PUM series, to Mitsubishi’s PLC (MELSEC-Q/A/AnS/FX series) without program. High-speed communication of maximum 230.4kbps can be performed via RS-232C, RS-422 or RS-485 interface. Also,...
  • Page 2: Connected Devices

    PUMCM 2. Connected devices • MELSEC-Q series Communication port Device Type QJ71C24, RS-232C RS-422/485 QJ71C24N (D-sub 9P) (2-piece socket block) Q-compatible serial QJ71C24-R2, RS-232C RS-232C communication unit QJ71C24N-R2 (D-sub 9P) (D-sub 9P) RS-422/485 RS-422/485 QJ71C24N-R4 (2-piece plug-in connector socket block) (2-piece plug-in connector socket block) •...
  • Page 3: Display Configuration

    MELSEC-FX series 500m or less RS-232C/RS-422/RS485 Within the devace DIP SW (6bit) × 1 (6) Recommended cable: Operation mode KFPEV-SB2P 0.5sq / FUJI ELECTRIC CABLE CO., LTD 5. Power outage (7) Data format: Start bit1, data bit 8, (1) Impact of power outage: Parity even/odd/none Outage of 2ms or less;...
  • Page 4: Code Symbols

    Program error monitoring by watch dog timer 11. Loader software 7. Structure (1) Distribution medium: Free download from Fuji Electric Systems (1) Installation method: HP (http://www.fic-net.jp) DIN rail mounting or mounting with M3 (2) Recommended operating environments screws inside a cabinet DOS/V (PC-AT compatible) (2) Dimensions: 30 (W) ×...
  • Page 5 OUTLINE DIAGRAM (Unit : mm) Front terminal cover (option) (10) Base part (Main unit is detached) Terminal block (at attach/detach) Hole for screw mounting LOADER STATION DIN rail Terminal screw M3 Terminal screw M3 Hole for screw mounting At mounting to the DIN rail Main unit (at attach/detach) DIN rail fixture...
  • Page 6: Terminal Connection Diagram

    PUMCM TERMINAL CONNECTION DIAGRAM Loader interface (RS-232C) LOADER I2.5 3-pole miniature plug STATION RS-485 RS-232C RS-422 Don’t Don’t connect connect Don’t connect Don’t connect Don’t connect Don’t connect Base part Power − 24V DC Don’t connect...
  • Page 7 Programless communication module status Contents Reading out/Writing data setting range Factory-set value Register No. Setting faults 0101h: St. No. configuration SW is invalid value − 30232 0102h: DIP SW is invalid value 0201h: PLC communication speed is invalid value 0202h: PLC communication data length is invalid value 0203h: MC protocol is invalid value 0204h: PLC communication inter-cycle time is invalid value 0205h: PLC communication starting time is invalid value...
  • Page 8 However, the parameters marked * in the "Entry ban" column cannot be set. &DXWLRQ RQ 6DIHW\ %HIRUH XVLQJ WKLV SURGXFW EH VXUH WR UHDG LWV LQVWUXFWLRQ PDQXDO LQ DGYDQFH Fuji Electric Your distributor: Coulton Instrumentation Ltd 17 Somerford Business Park, Christchurch, BH23 3RU, UK Tel: +44 1202 480 303 E-mail: sales@coulton.com...

Table of Contents