[Ar] Anti-Reset Windup (037) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

Anti-reset windup (037)
AR
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Anti-reset windup is a function that limits the range of valid integration to control overshooting.
Setting range
0 to 100%FS
The anti-reset windup function ([AR]) disables the integration when the PV falls outside of the Ar set range that
is centered around SV. It is automatically set to the optimum value when auto-tuning is activated.
PV
AR value
SV
AR value
[Setting example] Changing the anti-reset windup to 500°C –––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
In this zone, the integration
is disabled.
In this zone, the integration
is carried out.
In this zone, the integration
is disabled.
t
Press and hold the
key for about three seconds during the SV/PV display.
➔ appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
.
keys to change " 100 " to " 500 ."
35
2nd block parameter