3Rd Block Parameter; [P-N1] Control Action (090) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

3-3 3rd block parameter

P-N1 Control action (090)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This parameter specifies the control action and the output when an event occurs.
Control action
Setpoint
0
Reverse
1
2
Direct
3
* The output during burnout is as follows.
Lower limit: The output is set to OFF, or 4mA or less.
Upper limit: The output is set to ON, or 20mA or more.
[Setting example] –––––––––––––––––––––––––––––––––––––––––––––––––––
Changing the "Reverse/Lower limit for burn-out output" to the "Direct/Upper limit
for burn-out output"
Display
1.
2.
3.
4.
5.
Burn-out output*
Lower limit
Upper limit
Lower limit
Upper limit
Press and hold the
key for about five seconds during the SV/PV display.
appears.
Press the
key.
➔ The setpoint starts blinking.
Press the
key to change " 0 " to " 3 ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
57
3rd block parameter

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pxf4

Table of Contents