A1Op A2Op Alarm 1, 2 Options (101, 102) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

A2oP Alarm 1, 2 options (101, 102)
A1oP
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
You can set the optional functions to the alarm 1 and the alarm 2, if you need. The three types of optional functions
are assigned for each bit.
bit0
bit1
bit2
bit
Alarm latch:
bit0
Latches (maintains) the state when an event occurs.
Input error alarm:
Outputs when an input error ("UUUU" or "LLLL" is displayed) occurs.
bit1
Set the alarm type to " 0 " to use this function.
Inverted output function:
bit2
Inverts the output and open the contact during an event occurs.
[Setting example] ––––––––––––––––––––––––––––––––––––––––––––––––––
Adding the alarm latch and the converted output function to the alarm 1
Display
1.
2.
3.
4.
5.
6.
Function
Press and hold the
key for about five seconds during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
.
keys to change " 000 " to " 101 ."
61
3rd block parameter
Setpoint
0 (OFF)
1 (ON)
0 (OFF)
1 (ON)
0 (OFF)
1 (ON)