[Rcj] Rcj (Cold Junction Compensation) Setting (111) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

RCJ RCJ (Cold junction compensation) setting (111)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This is the procedure for turning the cold junction compensation on or off when using the input from a
thermocouple sensor.
Description
Setpoint
oN
Cold junction compensation on
oFF
Cold junction compensation off
This setting should be left " oN " during normal operation. It should only be turned off when cold junction
compensation is being performed externally or you wish to record temperature differences.
[Setting example] Setting the cold junction compensation to OFF –––––––––––––
Display
1.
2.
3.
4.
5.
6.
Press and hold the
key for about five seconds during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
.
keys to change " oN " to " oFF ."
65
3rd block parameter