FLo1 MV1 during FALT (146)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to specify the control output value when the controller falls into FALT (input error).
Setting range
-5.0 to 105.0%
[Setting example] Setting the OUT1 during FALT to 5% –––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Press and hold the
key for about five seconds during the SV/PV display.
appears.
➔
➔
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
➔
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
➔
Operating procedure
.
keys to change " -5.0 " to " 5.0 ."
71
3rd block parameter