Parameter functions and setting procedure
bAL Output convergence value (036)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Output convergence value is a function that adds an offset to MV value.
Setting range
-100 to 100%
By this function, the [bAL] offset is added to original MV which is the result of PID calculation determined by
●
PV and SV, and the total value is emitted as MV.
(The factory default setting is 0%.)
MV
100%
bAL=0%
40%
Proportional
SV
band
[Setting example] Changing Output convergence value from 0.0% to 3.0% –––––
Display
1.
2.
3.
4.
5.
6.
50%
bAL=40%
PV
Press and hold the
➔ appears.
➔
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
➔
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
➔
Operating procedure
key for about three seconds during the SV/PV display.
.
keys to change " 0.0 " to " 3.0 ."
34