[Bal] Output Convergence Value (036) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

Parameter functions and setting procedure
bAL Output convergence value (036)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Output convergence value is a function that adds an offset to MV value.
Setting range
-100 to 100%
By this function, the [bAL] offset is added to original MV which is the result of PID calculation determined by
PV and SV, and the total value is emitted as MV.
(The factory default setting is 0%.)
MV
100%
bAL=0%
40%
Proportional
SV
band
[Setting example] Changing Output convergence value from 0.0% to 3.0% –––––
Display
1.
2.
3.
4.
5.
6.
50%
bAL=40%
PV
Press and hold the
➔ appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
,
or
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
key for about three seconds during the SV/PV display.
.
keys to change " 0.0 " to " 3.0 ."
34