[P-N2] Input Signal Code (043) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

Parameter functions and setting procedure
P-N2 Input signal code (043)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
Allows you to select PV input source from thermocouples, RTD, and others.
Setpoint
JPt
RTD JPt100
RTD Pt100
Pt
J
Thermocouple J
K
Thermocouple K
Thermocouple R
R
b
Thermocouple B
S
Thermocouple S
Thermocouple T
t
E
Thermocouple E
L
Thermocouple L
The connection to the terminal block differs with types of input (thermocouple/
RTD/voltage or current input). Check the Instruction Manual.
Power-cycle the controller after you change the input type setting.
[Setting example] Changing the input from thermocouple K to thermocouple R ––
Display
1.
2.
3.
4.
5.
6.
Description
Press and hold the
key for about three seconds during the SV/PV display.
➔ appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
or
keys to change " K " to " R ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Setpoint
N
Thermocouple N
Thermocouple PL-II
PL-2
W
Thermocouple W
0-5V
0 to 5 V DC
1 to 5 V DC
1-5V
0-10
0 to 10 V DC
2-10
2 to 10 V DC
0 to 20 mA DC
0-20
4-20
4 to 20 mA DC
U
Thermocouple U
MV
MV
Operating procedure
42
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pxf4