tC
Cycle time of control output 1 (041)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
When using contact output and SSR drive output with PV input inside the
proportional band, output will switch between ON and OFF at regular intervals.
Setting range
1 to 150 sec
The following are the recommended settings for each control output.
The shorter the proportional cycle, the finer the control. However, shorter proportional cycles
also shorten the lifespan of the contact points and operating device. Keep a balance between
Contact
output
controllability and controller lifespan when adjusting the proportional cycles.
Approx.: 30 sec
Because there are no mechanical parts, use a short proportional cycle if the operating device is
SSR drive
working properly.
output
Approx.: 1 or 2 seconds
The proportional cycle for the current output is same as the blinking cycle of OUT
indicator (approximately 1 second).
[Setting example] Setting OUT1 proportional cycle to 60 sec ––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Press and hold the
key for about three seconds during the SV/PV display.
➔ appears.
Press the
key to display
Press the
key.
➔ The setpoint starts blinking.
Press the
or
keys to change " 30 " to " 60 ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔ The screen returns to the SV/PV display.
Operating procedure
.
41
2nd block parameter
Output ON
Proportional
cycle
Proportional
cycle