[Hys] Hysteresis Range For On/Off Control (033) - Fuji Electric Micro-Controller X Socket type Operation Manual

Digital temperature controller
Table of Contents

Advertisement

Parameter functions and setting procedure
HyS Hysteresis range for ON/OFF control (033)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
If you set the control method parameter [CtRL] to " oNoF ," set the hysteresis for on/off control in this parameter.
Setting range
0 to 50%FS
The controllability varies with the size of the hysteresis.
Small hysteresis
Large hysteresis
The relationship between SV and hysteresis in normal and reverse operation is shown below.
Reverse
Process
Value
SV
PV<SV
ON
Control
Output
OFF
During ON/OFF control, the [i] and [d] settings do not affect control.
If the hysteresis width is narrow, and PV and SV are nearly equal, the output may frequently switch on and off.
Note that it may affect the life of the contact.
Related parameters: Control algorithm [CtRL] (see page 36)
High-precision control
Frequency of output relays is high, so lifespan becomes short.
Low-precision control
Frequency of output relays is low, so lifespan is relatively long.
PV
HYS
PV>SV
Normal
Process
Value
SV
t
ON
Control
Output
OFF
32
PV
PV>SV
PV<SV
HYS
t