Parameter functions and setting procedure
dSPt PV/SV display OFF (148)
[Description] –––––––––––––––––––––––––––––––––––––––––––––––––––––––
This parameter is used to manually turn off the PV, SV, and LED lamps on PV/SV screen.
Setpoint
PV, SV, and LED lamps stay ON
0
1
SV display OFF
PV display OFF
2
3
PV and SV displays OFF
4
PV, SV, and LED lamps OFF (all off)
SV display OFF (relights for 5 sec by pressing any key)
5
6
PV display OFF (relights for 5 sec by pressing any key)
7
PV and SV displays OFF (relights for 5 sec by pressing any key)
8
PV, SV, and LED lamps OFF (all off) (relights for 5 sec by pressing any key)
If an input error or an alarm occurs during the settings 5 to 8, the displays and lamps stay ON even after 5 seconds.
If an input error or an alarm occurs during the settings 5 to 8, PV and/or SV will be turned on again.
[Setting example] Turning off the PV display –––––––––––––––––––––––––––––
Display
1.
2.
3.
4.
5.
6.
Function
Press and hold the
key for about five seconds during the SV/PV display.
appears.
Press the
key to display
Press the
key.
➔The setpoint starts blinking.
Press the
key to change " 0 " to " 2 ."
Press the
key or wait for three seconds to save the change.
Press the
key.
➔The screen returns to the SV/PV display.
72
Operating procedure
.