Fuji Electric Micro-Controller X Socket type Operation Manual page 39

Digital temperature controller
Table of Contents

Advertisement

(2) PID control (Pid)
PID control starts when the parameter [CtRL] is " Pid." PID control calculate Pid and output the result according to
the set values of the parameters [P], [i], [d], and [AR]. (-5 to 105%)
Each parameter can be set either by manually tuning the values or by running auto-tuning ([AT]) to automatically
set the values.
Related parameters: Auto-tuning [At] (see page 25)
(3) Fuzzy control (FUZY)
This control minimizes the overshoot compared to normal PID. Fuzzy control can only be used after auto-tuning
has been activated and a PID set.
Related parameters: Auto-tuning [At] (see page 25)
(4) Self tuning control (SELF)
Adds controls while automatically calculating PID to meet the
control target or changing SV. Self-tuning is especially effective
for situations when a high level of control is not needed, but auto-
tuning cannot be run due to frequent changes in the control target
conditions. If a high degree of control is required, select PID
control, fuzzy control or PID2 control.
The equipment will not be tuned properly if power is turned on
first.
When redoing the self-tuning settings, first set the control method
to PID (" Pid "), and then set back to self-tuning.
Conditions where self-tuning can be used
When temperature rises right after the power is turned on
When temperature rises after SV change (or when the controller judges it necessary)
When the controller judges it necessary because the control has become unstable
Conditions where self-tuning cannot be used
During standby
During ON/OFF (2-position) control
During auto-tuning
During ramp soak operation
When input error occurs
When any of the [P], [i], [d], or [AR] parameters have been manually configured
During manual mode
During soft start
Conditions where self-tuning is halted
When SV is changed (including when SV is changed by the ramp soak function, remote SV function, or ramp
SV.)
When self-tuning has not finished after running for nine or more hours
Set value
SV
Dead time
37
2nd block parameter
Tuning
Delay
t