Cisco ONS 15454 Hardware Installation Manual page 272

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

DLP-G596 Connect Office Power (AC) to the ONS 15454 M2 Shelf
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
Note
This product is intended for use on the TN and TT power systems.
Warning
When installing or replacing the unit, the ground connection must always be made first and disconnected
last. Statement 1046
Warning
This equipment shall be connected to AC mains provided with a surge protective device (SPD) at the
service equipment complying with NFPA 70, the National Electrical Code (NEC). Statement 7012
Caution
The ONS 15454 M2 relies on the protective devices in the building installation to protect against short circuit,
overcurrent and ground faults. Ensure that the protective devices are properly rated and comply with national
and local codes.
Note
Not more than 7 feet (2 m) of the power supply cable should be exposed between the equipment and the fiber
storage tray.
Cisco ONS 15454 Hardware Installation Guide
242
• #2 Phillips Dynamometric screwdriver
• Medium slot-head screwdriver
• Small slot-head screwdriver
• Wire wrapper
• Wire cutters
• Wire strippers
• Crimp tool
• Fuse panel
• Ground cable 13.3-mm² (#6 AWG) stranded. The PIDs of the power cables
are listed in
Table 30: PIDs for AC Power Cables, on page
NTP-G266 Install the ONS 15454 M2 Shelf, on page
• Connect the chassis to the office ground. For detailed instructions on how
to ground the chassis, refer to the
Guide for Cisco CPT and Cisco ONS Platforms
NTP-G270 Open and Remove the Standard Door of the ONS 15454 M2
Shelf, on page
218.
NTP-G267 Install the Power Module in the ONS 15454 M2 Shelf, on page
230.
Required
Onsite
None
Installing the ONS 15454 M2 Shelf
244.
194.
Electrostatic Discharge and Grounding
.

Advertisement

Table of Contents
loading

Table of Contents